HomeProuductsUKOOA Offshore & Marine Cables

 UKOOA TYPE GM / TYPE GP 150/250V Fire Resistant

Application

These cables are designed for fixed installation for control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.

Standards

BS 6883/BS 7917/UKOOA
IEC 60331-21
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2

Construction

Conductors Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228.
Fire Protection Mica glass tape
Insulation EPR complying with BS7655 GP4 
Drain Wire Tinned copper drain wire 
Individual Screen Aluminium mylar tape screen
Bedding EVA - SW4 compound complying with BS 7655 
Armour  Galvanised steel wire braid to BS 6883 
Outer Sheath  EVA - SW4 compound complying with BS 7655 (TYPE GM: Blue; TYPE GP: Grey).

Dimensions and Weight

Construction No. of cores×Cross section(mm²) Nominal Insulation Thickness mm Nominal Thickness of Inner Sheath mm Nominal Thickness of Outer Sheath mm Mominal Overall Diameter mm Approx. Weight kg/km
3×2×0.75 0.8 1.2 1.4

18.6

580
7×2×0.75 0.8 1.4 1.6

23.2

915
12×2×0.75 0.8 1.6 1.8

29.7

1420
20×2×0.75 0.8 2.1 2.7

40.1

2905
3×3×0.75 0.8 1.3 1.5

20.4

700
7×3×0.75 0.8 1.5 1.7

26.6

1180
12×3×0.75 0.8 1.9 2.2

38.5

2550
1×4×0.75 0.8 1.2 1.3

14.6

360
1×2×1.0 0.8 1.0 1.2

13.0

295
1×3×1.0 0.8 1.0 1.2

13.6

330
1×4×1.0 0.8 1.0 1.3

15.9

380
3×2×1.5 0.8 1.3 1.4

21.6

732
7×2×1.5 0.8 1.4 1.6

27.8

1242
12×2×1.5 0.8 1.7 1.9

36.4

2039
3×3×1.5 0.8 1.3 1.5

24.5

780
7×3×1.5 0.8 1.5 1.7

32.1

1409
12×3×1.5 0.8 1.8 2.0

43.9

2301